IEC Elektrik | 75 | 150 | 275 | 320 | 385 | 440 | |
Voltan AC Nominal (50/60Hz) | Uo/ Un | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Voltan Kendalian Berterusan Maksimum (AC) | Uc | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Arus Pelepasan Nominal (8/20 μs) | In | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
Arus Pelepasan Maksimum (8/20 μs) | Imaks | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Tahap Perlindungan Voltan | Up | 0.2 kV | 0.6 kV | 1.3 kV | 1.5 kV | 1.5 kV | 1.8 kV |
Masa tindak balas | tA | < 25 ns | |||||
Fius Sandaran (maks) | 125 A gL / gG | ||||||
Penilaian Arus Litar pintas (AC) | ISCCR | 10 kA | |||||
TOV Tahan 5s | UT | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | UT | 115V | 230V | 440V | 440V | 440V | 765V |
mod | Bertahan | Bertahan | Selamat Gagal | Selamat Gagal | Selamat Gagal | Selamat Gagal | |
Mekanikal & Alam Sekitar | |||||||
Julat Suhu Operasi | Ta | -40ºF hingga +158ºF [-40ºC hingga +70ºC] | |||||
Kelembapan Operasi yang Dibenarkan | RH | 5%...95% | |||||
Tekanan atmosfera dan ketinggian | 80k Pa ... 106k Pa / -500 m.....2000 m | ||||||
Tork Skru Terminal | Mmaks | 39.9 Ibf ·dalam [4.5 Nm] | |||||
Keratan Rentas Konduktor (maks) | 2 AWG (Pepejal, Terkandas) / 4 AWG (Fleksibel) | ||||||
35 mm2 (Pepejal, Terkandas) / 25 mm2(Fleksibel) | |||||||
Melekap | Rel DIN 35 mm, EN 60715 | ||||||
Darjah Perlindungan | IP 20 (terbina dalam) | ||||||
Bahan Perumahan | Termoplastik: Darjah Pemadaman UL 94 V-0 | ||||||
Perlindungan Terma | ya | ||||||
Keadaan Operasi / Petunjuk Kerosakan | Hijau ok / Merah cacat | ||||||
Kenalan Jauh (RC)Keupayaan Penukaran RC Keratan Rentas Konduktor RC (maks) | AC Pilihan: 250V / 0.5 A;DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A16 AWG (Pepejal) / 1.5 mm2(Pepejal) |
Fokus untuk menyediakan penyelesaian mong pu selama 5 tahun.